Amo, Indiana Fume Extraction Arm Mounting and Supports

Amo, Indiana Fume Extraction Arm Mounting and Supports

Fume extraction arms are continually moved, extended, and rotated, requiring them to be rigidly supported and mounted securely. A few factors affect mounting location: 1) the location of the fume source, 2) the coverage area for where the arm is used 3) the central system duct where the fume arm is connected.

Mounting options include:

Wall Mount - With duct systems running against a wall, mounting the arm (s) with brackets secured to a block wall or column is typical. If the central system duct is along the ceiling, on an outside wall, or mid-wall, there are designed brackets to fix the arm in place.

Bench Mount - Exhaust duct running along the floor allows mounting to a bench or tabletop. This mount has a standard option bracket for attaching the arm. Another standard bench mount is on a portable air filter or dust collector.

Ceiling Mount - Mounting the arms in the ceiling is an option if joists are present. A support weldment could be fabricated if a ceiling mount is a requirement. For low-weight short arms, the installation contractor can fabricate a wood fixture.

Stanchion Mount - When arms are located in the center of a facility having high bay areas, a stanchion will allow the mounting of an arm and hold it rigidly in place.

Exhaust Fans for Fume Extraction Arms in Amo

Industrial exhaust system arms often need a connection to an exhaust fan for isolated applications or when needed for additional static resistance when connecting to an existing duct system. Fan CFM and static pressure must be examined in both cases to maintain system performance. When coupling with an exhaust fan, it should be constructed of similar or compatible materials to the extraction arm.

Cast Aluminum Pressure Blowers

Cast aluminum pressure blowers are typically supplied by manufacturers where there is a non-corrosive airstream. They are light, come in a wide range of designs, are compact, and are AMCA B spark-resistant as standard. Motors are available in single and three-phase TEFC and EXP frames.

Carbon Steel Fume Exhauster

If conditions of the airstream are suitable, a carbon steel painted fan is selected in a direct drive arrangement with a horizontal mount configuration that requires minimal space. Steel blowers have the option for AMCA construction up to AMCA A and 304 and 316 SS construction. Motors are available in single and three-phase TEFC and EXP frames.

Industrial Plastic Fume Exhaust Fans

Corrosive environments require materials of construction that will not degrade over time. Plastic construction is misunderstood as fragile, but industrial-grade designs are compatible with the harshest environment. The plastics typically used for construction are PVC or polypropylene (P.P.) and are an excellent choice for the efficient conveyance of corrosive, chemically laden, humid, or polluted gases, fumes, and air. Motors are available in single and three-phase TEFC and EXP frames.

Fume Extraction Arm Exhaust Fans in Amo
Amo, Indiana Stainless Steel Extraction Arms

Amo, Indiana Stainless Steel Extraction Arms

Aggressive airstream chemistry may require the arms to be constructed of 304 stainless steel. The tubing and hood are stainless, with external adjustment joints at the hood and swivel joints. Arm assemblies have a wall mounting bracket and an internal damper for airflow adjustment and shutoff. The standard flex hose at the joints is an FDA Pur Antistatic hose. Stainless steel arm tube diameters vary from three to eight inches, and arm lengths from three feet up to fourteen feet, all suitable for washdown applications. 316 stainless steel construction is an available option.

  • Arm diameters include 3", 4", 5", 6", and 8", and arm lengths include 3', 5', 7', 8', 10', and 14'.
  • Available in hanging and benchtop models.
  • External joints are anodized aluminum.
  • Optional fume exhaust fans in aluminum, carbon steel, or PVC.
  • Tubes, hood, internal shutoff damper, and duct connection collar are all constructed of 304SS
  • Clear anti-static FDA hose rated for 200 degrees Fahrenheit.
  • 304 SS grab handle on the hood for easy mobility and positioning.

Amo IN Fume Extraction Arms

Industrial exhaust systems for capturing smoke, fume, dust, high-temperature air, and corrosive gases.

Amo, Indiana Weld Fume Extraction Arm

Amo, Indiana Weld Fume Extraction Arm

The demand for weld smoke extraction arms is always high and mandates an arm category. Depending on the application, different designs use either smooth wall or flex hose tubing. Both designs use external positioning joints and a hood with an internal adjustable damper. The units are typically wall-mounted but have ceiling and floor support bracket options. Arm diameter options range from six to eight inches, and arm lengths vary from three feet up to thirty-six feet. Personal weld fume packages include a single extraction arm, exhaust fan, and air filter.

  • Optional fume exhaust fans in aluminum, carbon steel, or PVC.
  • Low-pressure drop
  • Arm diameters include 3", 4", 5", 6", and 8", and arm lengths include 3', 5', 7', 8', 10', 14', 16', 23', 30', and 36'.
  • Shut off dampers built internally.
  • Standard units include a wall bracket. Ceiling mount options are available.
General Purpose Amo, Indiana Industrial Extraction Arm

"General Purpose" Amo, Indiana Industrial Extraction Arm

We label these arms a standard issue because they can be universally applied to most fume and dust extraction applications. The general-purpose arm is suitable for capturing smoke, dust, or any non-corrosive product. They are constructed of smooth powder-coated steel or aluminum tubing, a capture hood with adjustment grips, flex hose joint covers, and external adjustment brackets for the hood and swivel joints. The assemblies come standard with a wall mounting bracket but also have ceiling and floor support brackets available. An internal damper is included for airflow adjustment or shutoff. The arm mounting brackets allow for 180⁰ and 360⁰ rotation. Arm diameter options range from three to ten inches, and arm lengths vary from three to thirty-two feet. The maximum airstream temperature for these arms is about 180 degrees Fahrenheit.

Features and options:

  • The wall bracket is powder-coated black.
  • A shutoff damper is built into the lower tube.
  • Arm diameters include 3", 4", 5", 6", and 8", and arm lengths include 3', 5', 7', 8', 10', and 14'.
  • An optional fume exhaust fan in aluminum, carbon steel, or PVC.
  • Grab handle around the hood that is aluminum powder-coated black.
  • Includes duct connection collar
  • Black hose rated for 195 degrees Fahrenheit (intermittent 260 degrees Fahrenheit)